Image is illustrative
|
ProfiBus OLM/G12 V4.0 Optical Link Module, 1 RS485, 2 glass FOC interfaces (4 BFOC sockets), up to 2850m, signaling contact, measuring output Code:
6GK1503-3CB00
Price (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.4358 kg/pc
|
Volume:
0.0013 m3/pc
|
|
|
|
|
ProfiBus OLM/G12 V4.0 Optical Link Module, 1 RS485 ˄2 glass FOC interfaces (4 BFOC sockets), up to 2850m, signaling contact ˄measuring output, SiemensSIMATIC DP, interface DP/PA-Link and ET200M IM153-2 HF for extended temperature range for max. 12 S7-300 modules with redundancy capability, Timestamping suitable for isochronous mode New features: up to 12 modules can be used Slave Initiative for Drive ES and Switch ES Expanded quantity structure for HART auxiliary variables Operation of the 64-channel modules 32 signals / slot +++ Observe compatibility instructions in manual +++
General information |
Product type designation |
IM 153-2 HF |
Firmware version |
V6.0.0 |
Vendor identification (VendorID) |
801Eh |
Supply voltage |
Rated value (DC) |
|
● 24 V DC |
Yes |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
external protection for power supply lines (recommendation) |
2,5 A |
Mains buffering |
● Mains/voltage failure stored energy time |
5 ms |
Input current |
Current consumption, max. |
650 mA |
Inrush current, typ. |
3 A |
I²t |
0.1 A²·s |
Output current |
for backplane bus (5 V DC), max. |
1.5 A |
Power loss |
Power loss, typ. |
5.5 W |
Address area |
Addressing volume |
● Inputs |
244 byte |
● Outputs |
244 byte |
Hardware configuration |
Number of modules per DP slave interface, max. |
12 |
Time stamping |
Accuracy |
1 ms; 1ms at up to 8 modules; 10ms at up to 12 modules |
Number of message buffers |
15 |
Messages per message buffer |
20 |
Number of stampable digital inputs, max. |
128; Max. 128 signals/station; max. 32 signals/slot |
Time format |
RFC 1119 |
Time resolution |
0.466 ns |
Time interval for transmitting the message buffer if a message is present |
1 000 ms |
Time stamp on signal change |
rising / falling edge as signal entering or exiting |
Interfaces |
Transmission procedure |
RS 485 |
PROFIBUS DP |
● Node addresses |
1 to 125 permitted |
● automatic detection of transmission rate |
Yes |
● Output current, max. |
70 mA |
● Transmission rate, max. |
12 Mbit/s |
● SYNC capability |
Yes |
● FREEZE capability |
Yes |
● Direct data exchange (slave-to-slave communication) |
Yes; as publisher with all IO, as subscriber with F-IO only |
● Design of electrical connection of PROFIBUS interface |
9-pin sub D |
1. Interface |
PROFIBUS DP slave |
● GSD file |
SI05801E.GSG |
● automatic baud rate search |
Yes |
Protocols |
Bus protocol/transmission protocol |
PROFIBUS DP to EN 50170 |
Potential separation |
Potential separation exists |
Yes |
Isolation |
Isolation tested with |
Isolation voltage 500 V |
Degree and class of protection |
IP degree of protection |
IP20 |
Ambient conditions |
Altitude during operation relating to sea level |
● Installation altitude above sea level, max. |
3 000 m |
Configuration |
Configuration software |
● STEP 7 |
Yes; STEP 7 / COM PROFIBUS / non-Siemens tools via GSD file |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
117 mm |
Weights |
Weight, approx. |
360 g |
last modified: |
11/10/2018 |
|
File description
|