Image is illustrative
|
Digital Multifunction Meter MFM384, 1p2w/3p3w/3p4w, input 1/5A 100V (10kA/V)/ 1/5A 100..500VAC, prog. CT/PT, V/A/P/PF/Wp/Wq/Ws, pulse output, RS485, ModBus RTU, 4x4, 8digits LCD w. backlight, sv 100..230VAC, ■99x99/□92x92, IP65, Selec Code:
MFM384-C-CU
Price
Manufacturer
:
Availability:
14 days
|
Weight:
0.395 kg/pc
|
Volume:
0.0005 m3/pc
|
|
|
|
|
Digital Multifunction Meter MFM384, 1p2w/3p3w/3p4w, input 1/5A 100V (10kA/V)/ 1/5A 100..500VAC, prog. CT/PT, V/A/P/PF/Wp/Wq/Ws, pulse output, RS485 ^ModBus RTU, 4x4 ^8digits LCD w. backlight, sv 100..230VAC, ■99x99/□92x92, IP65, Selec
Funtions
3Ø (True rms) Voltage
3Ø (True rms) Current
3Ø Power (Active, Reactive, Apparent)
3Ø Power Factor
Frequency
Energy (Active, Reactive, Apparent)
Programmable CT/PT Primary/Secondary
Modbus RTU Communication (RS485) (Optional)
Pulse Output
Demand (Min/Max Active Power, Min/Max Reactive Power, Max Apparent Power)
|
FUNCTIONS |
- 3Ø (True rms) Voltage |
|
- 3Ø (True rms) Current |
|
- 3Ø Power (Active, Reactive, Apparent) |
|
- 3Ø Power Factor |
|
- Frequency |
|
- Energy (Active, Reactive, Apparent) |
|
- Programmable CT/PT Primary/Secondary |
|
- Modbus RTU Communication (RS485) (Optional) |
|
- Pulse Output |
|
- Demand (Min/Max Active Power, Min/Max Reactive Power, Max Apparent Power) |
|
|
Display |
Liquid crystal display with backlight |
Digits
|
4 rows of 4 digits, 1 row of 8 digits for energy display
Bargraph representation of current |
Input type |
3Ø - 3/4wire, 2 Ø - 3 wire, 1 Ø - 2 wire |
Rated input Voltage |
11 to 300V AC max phase to neutral, 50/60Hz
19 to 519V AC max phase to phase, 50/60Hz |
Voltage Burden (max) |
0.2VA @ 300V (L-N) |
Rated input Current |
10mA - 5A (6A max) (External CT must be connected for current more than 5A) |
Current Burden (max) |
0.5VA @ 5A per phase |
Frequency |
45 to 65 Hz |
Resolution |
For energy - 0.01k, 0.1k, 1k, 0.01M, 0.1M, 1M
(depending upon CT ratio X PT ratio)
For power, Voltage & Current-Auto resolution
For Power factor - 0.001 |
Accuracy Class |
Class 1 for Active / Reactive / Apparent energy
1% for Active / Reactive / Apparent power
±0.5% of FS for V L-L, VL-N, Avg.VL-N, Avg.VL-L, I, Avg. I
±0.1% for Frequency
±1% for Power factor and Avg. Power factor |
CT Primary |
1A / 5A upto 10,000A (Programmable for any Value)
Note: 1A or 5A depens upon the CT secondary |
CT Secondary |
1A or 5A (Programmable) |
PT Primary |
100V to 500kV (Programmable for any Value) |
PT Secondary |
100V to 500V AC (phase to phase) (Programmable for any Value) |
Supply Voltage |
85 to 270V AC (50/60Hz), (Power Consumption: Less than 8VA) |
Display Scrolling |
Automatic / Manual |
LCD/LED Parameter Indications |
1) Numerical display for all measured parameters
2) Percentage of current in bar graph form |
Display reset |
Available (password protected) |
Memory Retention of Energy |
10 years |
Output |
Pulse Output: Voltage range - External 24V DC max.
Current capacity - 100mA max.
Pulse width: 100ms ± 5 ms. |
Communication |
RS485 MADBUS Communication (Optional) |
Temperature / Humidity (non-condensing) |
Operating: -10°C to 55°C, Storage: -20°C to 75° / Upto 85% RH |
|
|
|