Pilt on illustreeriv
|
HART Multiplexer Slave KFD0-HMS-16, Pepperl+Fuchs Kood:
231291
Hind (indikatiivne)
Tootja
:
Saadavus:
21 päeva
|
Kaal:
0.1234 kg/tk
|
|
|
|
|
|
HART Multiplexer Slave KFD0-HMS-16, Pepperl+FuchsHART Multiplexer Slave KFD0-HMS-16
- 16-channel
- No external power required
- HART field device input (revision 5 to 7)
- Used with HART Multiplexer Master KFD2-HMM-16
- Up to SIL3 acc. to IEC 61508
Datasheet excerpt: Technical data of KFD0-HMS-16
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
Supply |
Connection | via 14-channel flat cable form master KFD2-HMM-16 |
HART signal channels (non-intrinsically safe) |
Conformity | HART field device input (revision 5 to 7) |
Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 |
Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) |
Terminating resistor | external 230 ... 500 Ω standard (up to 1000 Ω possible) |
Output voltage | ≥ 400 mV ss (with the terminator resistance specified above) |
Output resistance | 100 Ω or smaller, capacitive coupling |
Input impedance | according to HART specification |
Input voltage range | 0.08 ... 4 V ss ; typ. ± 5.2 V as local reference |
Indicators/settings |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Mass | approx. 100 g |
Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) , housing type B1 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
Certificate | PF 07 CERT 1143 X |
| Marking | II 3G Ex nA IIC T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
|
|
|
|
|