Image is illustrative
|
Digital Panel Meter N30P, 1ph power network meter, input 0..1/5A 0..100/400V, output pulse, RS485, analog, unit kV, sv 85..253VAC/DC, ■96x48mm/ □92x45mm, IP65, Lumel Code:
N30P-110400E0
Price
Manufacturer
:
Availability:
28 days
|
Weight:
0.38 kg/pc
|
Volume:
0.0012 m3/pc
|
|
|
|
|
Digital Panel Meter N30P, input 1/5A 100/400V, output pulse ^0/4..20mA/ 0..10V ^RS485, unit kV, LED display, progr. PD10, sv 85..253VAC/DC, ■72x72/ □68x68, IP65, Lumel
About
N30P meter is destined to measure: a.c. voltage, a.c. current, active, reactive and apparent power, cos φ, tg φ, φ, frequency, active, reactive and apparent energy, 15 min. active power, 10 min. voltage, 10 sec. frequency in single-phase power network.
- Input:
- current: 0...1 or 0...5A
- voltage: 0...100V or 0...400V
- Output: relay (4), analog (1), energy pulse (1), digital RS485/MODBUS (1)
- 3-colour display - red, green and orange programmable in three intervals of the measured value
- 14mm digit hight
- highlighted measuring units
- 4 alarm outputs with signalling by LED diodes, operating in 6 different modes,
- Conversion of any measured value into a 0/4…20mA or 0…10V analog signal,
- Storage of minimal and maximal values for all measured quantities,
- Meter programming from the keyboard or through the RS485 interface by means of free eCon software.
Parameters which can be reprogrammed are as follows:
- display colour, individually in three intervals,
- thresholds of displayed overflows,
- display precision of the result (decimal point),
- highlight of the unit,
- averaging time of the measurement,
- recounting of indications (individual characteristic).
- Supply: 85...253 V AC/DC or 20...40 V AC/DC
- Protection level from frontal side: IP65,
- External simension: 96 x 48 x 64mm.
|
|
|
|