|
|
Image is illustrative
|
Analogue Output Expansion Module MicroLogix, 4-ch., voltage/current, Allen-Bradley Code:
1762-OF4
Price (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.22 kg/pc
|
Volume:
0.0011 m3/pc
|
|
|
|
|
Analogue Output Expansion Module MicroLogix, 4-ch., Voltage/Current, Rockwell Automation
DESCRIPTIONS
MicroLogix™ Analog Output Module, Number Of Channels: 4 (Isolated, Single-Ended), Output: Resistive Load On Current Output: 0 - 500 OHM (Includes Wire Resistance), Load Range On Voltage Output: Greater Than 1 KOHM, Reactive Load Current Output: Less Than 0.1 MH, Reactive Load Voltage Output: Less Than 1 MFD, Voltage Rating: 0 - 10 V, Rated Working Voltage: 30 VAC/VDC, Maximum Overload At Input Terminals: Plus/Minus 35 VDC Continuous, Analog Normal Operating Range Voltage: 0 - 10 VDC, Full Scale Analog Range Voltage: 0 - 10.5 VDC, Current Rating: 4 - 20 MA, Output Protection: Plus/Minus 32 MA, Analog Normal Operating Range Current: 4 - 20 MA, Full Scale Analog Range Current: 0 - 21 MA, Isolation: 30 VAC/VDC Rated Working Voltage (IEC Class 2 Reinforced Insulation) Type Test: 500 VAC Or 707 VDC For 1 MIN, Enclosure: IP20, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ, Connection Cables: Belden 8761, Mounting: DIN Rail, Panel, Length: 1.58 IN, Width: 3.43 IN, Height: 3.54 IN, Temperature Rating: -32 To 131 DEG F, Environmental Conditions: Operating Humidity: 5 - 95% (Non-Condensing), Vibration - Operating: 10 - 500 HZ, 5 G, 0.030 IN Max Peak-To-Peak, Shock Operating: 30 G, Response Time: Open-Circuit Detection Time: 7 MS - 1.515 SEC, Accuracy: Plus/Minus 1.17% Full Scale At -20 to 65 DEG C, Plus/Minus 0.5% Full Scale At 25 DEG C, Power Dissipation: Heat Dissipation: 1.5 W, Bus Rating: Bus Current Load: 40 MA At 5 VDC, 165 MA At 24 VDC, Impedance: Cable Impedance: 25 OHM, Input Impedance: Greater Than 10 MOHM, Indicator: LED, Resolution: 12 Bits, Surge Transient Immunity: Plus/Minus 1 KV Shielded Line-Earth (CM) On Signal Ports, Standard/Approvals: C/US UL listed, CE marked, C-tick, GOST_R, KCC, marine-ABS, marine-BVS, marine-DNV, marine-GL, marine-LR, ROSTECHNADZOR
|
|
SPECIFICATIONS
- Item Name: Analog Output Module
- Sub Brand: MicroLogix™
- Number Of Channels: 4 (Isolated, Single-Ended)
- Output: Resistive Load On Current Output: 0 - 500 OHM (Includes Wire Resistance), Load Range On Voltage Output: Greater Than 1 KOHM, Reactive Load Current Output: Less Than 0.1 MH, Reactive Load Voltage Output: Less Than 1 MFD
- Voltage Rating: 0 - 10 V, Rated Working Voltage: 30 VAC/VDC, Maximum Overload At Input Terminals: Plus/Minus 35 VDC Continuous, Analog Normal Operating Range Voltage: 0 - 10 VDC, Full Scale Analog Range Voltage: 0 - 10.5 VDC
- Current Rating: 4 - 20 MA, Output Protection: Plus/Minus 32 MA, Analog Normal Operating Range Current: 4 - 20 MA, Full Scale Analog Range Current: 0 - 21 MA
- Isolation: 30 VAC/VDC Rated Working Voltage (IEC Class 2 Reinforced Insulation) Type Test: 500 VAC Or 707 VDC For 1 MIN
- Enclosure: IP20
- Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ
- Connection Cables: Belden 8761
- Mounting: DIN Rail, Panel
- Length: 1.58 IN
- Width: 3.43 IN
- Height: 3.54 IN
- Temperature Rating: -32 To 131 DEG F
- Environmental Conditions: Operating Humidity: 5 - 95% (Non-Condensing), Vibration - Operating: 10 - 500 HZ, 5 G, 0.030 IN Max Peak-To-Peak, Shock Operating: 30 G
- Response Time: Open-Circuit Detection Time: 7 MS - 1.515 SEC
- Accuracy: Plus/Minus 1.17% Full Scale At -20 to 65 DEG C, Plus/Minus 0.5% Full Scale At 25 DEG C
- Power Dissipation: Heat Dissipation: 1.5 W
- Indicator: LED
- Surge Transient Immunity: Plus/Minus 1 KV Shielded Line-Earth (CM) On Signal Ports
- Resolution: 12 Bits
- Impedance: Cable Impedance: 25 OHM, Input Impedance: Greater Than 10 MOHM
- Bus Rating: Bus Current Load: 40 MA At 5 VDC, 165 MA At 24 VDC
FEATURES
The 1762 MicroLogix expansion I/O modules are compatible with MicroLogix 1100, MicroLogix 1200, and MicroLogix 1400 controllers. Install the expansion I/O modules to the right of the controller, either on a panel with two mounting screws or on a DIN rail. Use analog I/O modules in many combinations, up to the maximum supported by the controller. The current loading capacity of the controller’s built-in power supply may limit the actual number of I/O modules that can be connected to the controller.
Integrated high-performance I/O bus
Software keying to prevent incorrect positioning within the system
Finger-safe terminal blocks for I/O wiring
Label to record I/O terminal designations
Network support includes EtherNet/IP, DeviceNet, and DH-485 (local only)
Standards: C/US UL listed, CE marked, C-tick, GOST_R, KCC, marine-ABS, marine-BVS, marine-DNV, marine-GL, marine-LR, ROSTECHNADZOR
|
|
|
|