|
|
Image is illustrative
|
Controller MicroLogix 1100, 16ports, 10DI 24VDC, 2AI 0..10V, 6RO, 120/240VAC, Rockwell Automation Code:
1763-L16BWA
Price (indicative)
Manufacturer
:
Availability:
ask for dd
|
Weight:
0.872 kg/pc
|
Volume:
0.0051 m3/pc
|
|
|
|
|
Controller MicroLogix 1100, 16ports, 10DI 24VDC, 2AI 0..10V, 6RO, 120/240VAC, Rockwell Automation
DESCRIPTIONS
MicroLogix™ Controller, Memory: 8 KB, Interface: Ethernet Port and Isolated RS-232/RS-485 Combo Port, DF1, DH-485, ASCII, Communication: Modbus RTU, EtherNet/IP Messaging, Number Of Channels: 18 (12 Input (10 Digital And 2 Analog), 6 Output), Mounting: DIN Rail, Panel, Input: Digital - On-State Voltage Range: 14 - 24 VDC/10 - 24 VDC, Off-State Voltage Range: 0 - 5 VDC, On-State Current: 8.8 MA At 24 VDC/8.5 MA At 24 VDC, Off-State Leakage Current: 1.5 MA, Analog - Voltage Input Range: 0 - 10 VDC - 1 LSB, Voltage Input Overvoltage Protection: 10.5 VDC, Output: Relay, For Hazardous Location - Maximum Controlled Load: 1080 VA, Current Per Group Common: 3 A, Current Per Controller: 18 A At 150/240 V, Load Current: 10 MA, For Non-Hazardous Location - Maximum Controlled Load: 1440 VA, Current Per Group Common: 5 A, Current Per Controller: 30 A At 150 V/20 A At 240 V, Response Time: Turn On/Off Time: 10 MS, Rfi Suppression: Radiated: 10 V/M, 26 To 1000 MHZ (Alternatively, 80 To 1000 MHZ), 80% Amplitude Modulation, 900 MHZ Keyed Carrier, Conducted: 10 V, 150 KHZ - 80 MHZ, Display: LCD, Length: 4.33 IN, Width: 3.43 IN, Height: 3-1/2 IN, Temperature Rating: -4 To 140 DEG F, Environmental Conditions: Operating Humidity: 5 - 95% (Non-Condensing), Vibration - Operating: 5 G, Relay Operation: 1.5 G, Shock - Operating Shock: 30 G, Relay Operation: 10 G, Non-Operating Shock: 40 G (DIN Mount)/50 G (Panel), Voltage Rating: 100 - 240 VAC At 47 - 63 HZ, Current Rating: Inrush: 25 A For 8 MS At 120 VAC, 4 A For 4 MS At 240 VAC, Communication Speed: 10/100 MBPS, Power Consumption: 52 VA, Standard/Approvals: UL listed, class 1, division 2, hazardous locations, goups A, B, C, D, CE marked, C-tick, GOST_R, KCC certified, marine-ABS, marine-BVS, marine-DNV, marine-GL, marine-KRS, marine-LR, ROSTECHNADZOR
|
|
SPECIFICATIONS
- Item Name: Controller
- Sub Brand: MicroLogix™
- Memory: 8 KB
- Interface: Ethernet Port and Isolated RS-232/RS-485 Combo Port, DF1, DH-485, ASCII
- Communication: Modbus RTU, EtherNet/IP Messaging
- Number Of Channels: 18 (12 Input (10 Digital And 2 Analog), 6 Output)
- ounting: DIN Rail, Panel
- Input: Digital - On-State Voltage Range: 14 - 24 VDC/10 - 24 VDC, Off-State Voltage Range: 0 - 5 VDC, On-State Current: 8.8 MA At 24 VDC/8.5 MA At 24 VDC, Off-State Leakage Current: 1.5 MA, Analog - Voltage Input Range: 0 - 10 VDC - 1 LSB, Voltage Input Overvoltage Protection: 10.5 VDC
- Output: Relay, For Hazardous Location - Maximum Controlled Load: 1080 VA, Current Per Group Common: 3 A, Current Per Controller: 18 A At 150/240 V, Load Current: 10 MA, For Non-Hazardous Location - Maximum Controlled Load: 1440 VA, Current Per Group Common: 5 A, Current Per Controller: 30 A At 150 V/20 A At 240 V
- Response Time: Turn On/Off Time: 10 MS
- Rfi Suppression: Radiated: 10 V/M, 26 To 1000 MHZ (Alternatively, 80 To 1000 MHZ), 80% Amplitude Modulation, 900 MHZ Keyed Carrier, Conducted: 10 V, 150 KHZ - 80 MHZ
- Display: LCD
- Length: 4.33 IN
- Width: 3.43 IN
- Height: 3-1/2 IN
- Temperature Rating: -4 To 140 DEG F
- Environmental Conditions: Operating Humidity: 5 - 95% (Non-Condensing), Vibration - Operating: 5 G, Relay Operation: 1.5 G, Shock - Operating Shock: 30 G, Relay Operation: 10 G, Non-Operating Shock: 40 G (DIN Mount)/50 G (Panel)
- Voltage Rating: 100 - 240 VAC At 47 - 63 HZ
- Current Rating: Inrush: 25 A For 8 MS At 120 VAC, 4 A For 4 MS At 240 VAC
- Communication Speed: 10/100 MBPS
- Power Consumption: 52 VA
FEATURES
There are 10 digital inputs, 6 digital outputs, and 2 analog inputs on every controller, with the ability to add digital, analog, RTD, and thermocouple modules to customize the controller for your application. On versions of the controller with DC inputs, there is a high-speed counter, and on the DC output version, two PTO/PWM (pulse train outputs and pulse width modulated) outputs, enabling the controller to support simple motion applications.
Built-in RTC, Online Editing, 1 HSC, 2 PTO/PWM, Up to 4 Expansion I/O
One embedded 20 KHZ high-speed counter (on controllers with DC inputs) - The built-in independent high-speed counter uses 32-bit integers for extended range, features 8 modes of operation, and supports direct control of outputs independent of program scan
Two 20 KHZ high-speed PTO/PWM outputs (on controllers with DC outputs)
Digital trim potentiometers - allow quick and easy adjustments of timers, counters, setpoints, and more
Program data security - data file download protection lets a program be reloaded into the controller without overwriting protected data
Floating point data files - to create data files that can contain up to 256 IEEE-754 floating point values
Memory modules - for backup provides protection and transportability for programs and data
Four interrupt inputs - interrupt inputs let the controller scan a specific program file (subroutine) when an input condition is detected from a sensor or field device
Real-time clock - embedded in every controller
Standards: UL listed, class 1, division 2, hazardous locations, groups A, B, C, D, CE marked, C-tick, GOST_R, KCC certified, marine-ABS, marine-BVS, marine-DNV, marine-GL, marine-KRS, marine-LR, ROSTECHNADZOR
|
|
|
|