Elit logo e-Elit - leading
electronic and automation component
online distributor
Est En
Elit shopping basket
Items: Total:
0
€0.00
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Control Desk SBA, 800Wx1000Hx400D, rear, front doors, upper panel, TS35, gas springs, mounting plate, adj. cable entry, doors w. ø3mm double bar closing system, CE/UL, IP55 IK10, NEMA12, grey
Control Desk SBA, 800Wx1000Hx400D, rear, front doors, upper panel, TS35, gas springs, mounting plate, adj. cable entry, doors w. ø3mm double bar closing system, CE/UL, IP55 IK10, NEMA12, grey



Simatic S7-1200, Analog Input, SM 1231, 4AI, ±10V, ±5V, ±2.5V, ±1.25/ 0/4..20mA, 15bit+sign bit
Image is illustrative
Simatic S7-1200, Analog Input, SM 1231, 4AI, ±10V, ±5V, ±2.5V, ±1.25/ 0/4..20mA, 15bit+sign bit
Code: 6ES7231-5ND32-0XB0
Price (indicative)
€367.90  /pc
Manufacturer :
Availability:
21 days
Weight:
0.1733 kg/pc
Volume:
0.0005 m3/pc
Quantity (pc):
Plus sign Minus sign
 

 

Simatic S7-1200, Analog Input, SM 1231, 4AI, ±10V, ±5V, ±2.5V, ±1.25/ 0/4..20mA, 15bit+sign bit, Siemens

SIMATIC S7-1200, Analog input, SM 1231, 4 AI, +/-10 V, +/-5 V, +/-2.5 V, +/-1.25 or 0-20 mA/4-20 mA, 15 bit+sign bit
General information
Product type designation SM 1231, AI 4x16 bit
Supply voltage
Rated value (DC)
● 24 V DC Yes
Input current
Current consumption, typ. 65 mA
from backplane bus 5 V DC, typ. 80 mA
Power loss
Power loss, typ. 1.8 W
Analog inputs
Number of analog inputs 4; Current or voltage differential inputs
permissible input voltage for voltage input (destruction limit), max. ±35 V
permissible input current for current input (destruction limit), max. 40 mA
Cycle time (all channels) max. 100 µs
Input ranges
● Voltage Yes; ±10V, ±5V, ±2.5V or ±1.25V
● Current Yes; 4 to 20 mA, 0 to 20 mA
● Thermocouple No
● Resistance thermometer No
● Resistance No
Input ranges (rated values), voltages
● -1.25 V to +1.25 V Yes
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) ≥1 MOhm
● -2.5 V to +2.5 V Yes
● Input resistance (-2.5 V to +2.5 V) ≥1 MOhm
● -5 V to +5 V Yes
● Input resistance (-5 V to +5 V) ≥1 MOhm
Input ranges (rated values), currents
● 0 to 20 mA Yes
● 4 mA to 20 mA Yes
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 15 bit; + sign
● Integration time, parameterizable Yes
● Interference voltage suppression for interference frequency f1 in Hz 40 dB, DC to 60 V for interference frequency 50 / 60 Hz
Smoothing of measured values
● parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Errors/accuracies
Temperature error (relative to input range), (+/-) 25 °C ±0.1% / ±0.3% total measurement range
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.1 %
● Current, relative to input range, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 12 V
Interrupts/diagnostics/status information
Alarms Yes
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes
Diagnostics indication LED
● for status of the inputs Yes
● for maintenance Yes
Degree and class of protection
Degree of protection acc. to EN 60529
● IP20 Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
FM approval Yes
RCM (formerly C-TICK) Yes
Marine approval Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Connection method
required front connector Yes
Mechanics/material
Enclosure material (front)
● Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 180 g