Elit logo e-Elit - leading
electronic and automation component
online distributor
Est En
Elit shopping basket
Items: Total:
0
€0.00
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Ethernet/IP Tap Stratix, dual port, 2-copper, 1-fiber port, 22..12AWG copper wire/ RJ45/ LC connector
Ethernet/IP Tap Stratix, dual port, 2-copper, 1-fiber port, 22..12AWG copper wire/ RJ45/ LC connector



DC UPS Module DUPS40, input 40A 24..29VDC, output charge current 2A| external battery 4..135AH 24VDC, 0..40A 21..29VDC, LED, relay contact 1A 30VDC, TS35
Image is illustrative
DC UPS Module DUPS40, input 40A 24..29VDC, output charge current 2A| external battery 4..135AH 24VDC, 0..40A 21..29VDC, LED, relay contact 1A 30VDC, TS35
Code: DUPS40
Price
€42.90  /pc
Manufacturer :
Availability:
14 days
Weight:
0.47 kg/pc
Volume:
0.0009 m3/pc
Quantity (pc):
Plus sign Minus sign
 

Overview
DUPS40 24V/40A DIN rail type uninterruptible DC-UPS module.
Features
Uninterruptible DC-UPS controller.
Parallel connection to DC BUS (power supply + DC-UPS module + batteries + load).
Suitable for 24V system, up to 40A.
2A battery charging current.
Allows 4Ah..135Ah lead-acid batteries.
Complete diagnostic and monitoring for DC BUS OK, battery discharge, battery fail.
LED indicator for signal status.
Protections: battery reverse polarity protection and short circuit (by internal detection).
Protections: battery discharge / over discharge current.
Cooling by free air convection.
3 years warranty.
Applications
Industrial control system.
Semiconductor fabrication equipment.
Factory automation.
Electro-mechanical apparatus.
Electrical
Normal input voltage 24VDC
Input voltage range 24..29VDC
Rated current 40A
Output voltage range 21..29VDC
Discharge current range 0..40A
Charging current 2A
Battery
Normal battery voltage 24VDC (2x12VDC in series or 1x24VDC)
Battery type Lead-acid battery
External battery capacities 4Ah..135Ah
Protection and status
Battery polarity Protection by internal detection, no damage, recovers automatically after fault condition is removed
Short circuit Protection by internal detection, no damage, external fuse is recommended
Over discharge current 42..46A, after 3sec, unit will cut-off battery discharging by relay
Battery deep discharge Cut-off battery discharging by relay
Relay contact rating 30VDC/1A resistive load
DC BUS OK LED (green): DC BUS OK, light; DC BUS fail: dark
Battery fail LED (red): battery over-discharge warning or battery broken; battery OK: dark
Battery discharge LED (yellow): battery discharging; battery not discharging or discharging current <2.0A: dark
Environment
Cooling Free air convection
Working temperature -30..+70°C
Working humidity 5..95%RH non-condensing
Storage temperature -40..+85°C
Dimensions
Dimensions (WxHxD) 63x123.2x113.5mm
 
 